Load influence on lissajous figure for online transformer winding diagnosis
Authors:
- 1 September 2016
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 1-4
Abstract
Research of transformer online monitoring technique for transformer winding deformation is of great significance. In this paper, a method to diagnosis transformer winding online is concerned. This method uses transformer's operation voltage and current to build an ellipse that is called Lissajous figure. Through Lissajous figure, winding deformation is able to be reflected sensitively and intuitively. However, change of transformer's load will affect the parameters of Lissajous figure as well. As to this problem, this paper concentrates on the influence of load on Lissajous figure. Research on the discipline that how Lissajous figure changes with the fluctuation of transformer's load is executed. The results show that the amplitude of load will cause the ellipse to magnify or diminish proportionally, but the power factor of load have no influence on the ellipse.Keywords
This publication has 4 references indexed in Scilit:
- A Novel Online Technique to Detect Power Transformer Winding FaultsIEEE Transactions on Power Delivery, 2012
- Case study: lessons learned from the failure of a new 230-kV transformer-cable terminationIEEE Electrical Insulation Magazine, 2010
- Apparatus for Online Power Transformer Winding Monitoring Using Bushing Tap InjectionIEEE Transactions on Power Delivery, 2009
- On-line detection of winding deformation2005