Influence of operating voltage on breakdown characteristics of HVDC GIL under impulse voltage
Authors:
- 1 May 2018
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 1006-1009
Abstract
In HVDC GIL, impulse overvoltage is not generated alone but generally superimposed on the DC operating voltage. Therefore, it is of great necessity to study the influence of DC operating voltage on breakdown characteristics of HVDC GIL under impulse voltage. In this paper, breakdown characteristics of GIL under superimposed voltage of DC and impulse are studied. The results indicate that pre-stressed DC voltage of positive polarity has little effect on the breakdown voltage of gas gap. When DC voltage is in negative polarity, the influence of DC voltage is related to the polarity of impulse voltage. Under superimposed voltage of negative DC and negative impulse, breakdown voltage is higher than that under impulse voltage alone. Under superimposed voltage of negative DC and positive impulse, breakdown characteristics of GIL depend on the size of the fixed particle. With the increase of particle length and decrease of particle radius, the influence of DC voltage becomes larger. Moreover, the light signal proves that the space charge produced in corona discharge under DC voltage has significant influence on the discharge process of gas gap under superimposed voltage. The results of the experiments show that superimposition of DC operating voltage and impulse voltage can be a critical condition for HVDC GIL, therefore superimposed test of DC and impulse is proposed to be part of on-site test for HVDC GIL to ensure the insulation ability under the service condition. Since up to now there is no valid standard for HVDC GIL, this research can serve as reference for the future formation of test standards.Keywords
This publication has 7 references indexed in Scilit:
- Direct Current Gas-Insulated Transmission LinesIEEE Transactions on Power Delivery, 2017
- Insulation characteristics of GIS insulators under lightning impulse with DC voltage superimposedIEEE Transactions on Dielectrics and Electrical Insulation, 2015
- State of the Art in Ultrahigh-Voltage TransmissionProceedings of the IEEE, 2011
- Evaluation of breakdown characteristics of gas insulated switchgears for non-standard lightning impulse waveforms under diverse conditionsIEEE Transactions on Dielectrics and Electrical Insulation, 2008
- DC dielectric characteristics and conception of insulation design for DC GISIEEE Transactions on Power Delivery, 1996
- Breakdown of SF/sub 6/ in non-uniform field gaps under combined DC fast oscillating impulse and standard lightning impulse voltagesIEEE Transactions on Electrical Insulation, 1993
- Effect of Space Charge on Electric Breakdown of Sulfur Hexafluoride in Nonuniform FieldsTransactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems, 1958