Discriminant-Analysis-Based Single-Phase Earth Fault Protection Using Improved PCA in Distribution Systems
Authors:
- 24 March 2015
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 30 (4) , 1974-1982
Abstract
This paper presents a new approach for single phase-earth fault protection in distribution systems. Traditional protection schemes are analyzed and compared with one another for effective fault feature extraction. The maximum-likelihood method is also carried out on several copula functions to find the optimal copula to fit the fault feature data. Then, copula rank correlation is calculated by the optimal copula, and the principal component analysis technique is improved to preprocess and reduce the dimension of the fault data by decomposing the copula rank correlation matrix instead of computing the eigenvalues and their eigenvectors of the covariance matrix. Finally, the distance discriminant function is defined and operation criterion is proposed, and distance discriminant analysis is used to discriminate the faulty feeder. Simulation results of a practical 10-kV distribution system show that the proposed approach of fault protection is able to achieve better identification accuracy than the hierarchical clustering algorithm and Fuzzy c-means algorithms-based approaches.Keywords
Funding Information
- National Natural Science Foundation of China
This publication has 24 references indexed in Scilit:
- The Directional Feature of Current Transients, Application in High-Speed Transmission-Line ProtectionIEEE Transactions on Power Delivery, 2013
- Protection system analysis using fault signatures in MalaysiaInternational Journal of Electrical Power & Energy Systems, 2013
- Research on Arc-grounding Overvoltage in the 10 kV Distribution SystemEnergy Procedia, 2012
- An Adaptive Approach Based on KPCA and SVM for Real-Time Fault Diagnosis of HVCBsIEEE Transactions on Power Delivery, 2011
- Using Integrated Model to Assess the Efficiency of Electric Distribution CompaniesIEEE Transactions on Power Systems, 2010
- A Traveling-Wave-Based Protection Technique Using Wavelet/PCA AnalysisIEEE Transactions on Power Delivery, 2010
- An adaptive inverse time-delay characteristic of the zero-sequence overvoltage protection for identification of the single-phase earth fault in the neutral non-effectively grounded power systems2009
- Ground fault protection in low voltage solidly grounded wye systems, need for protection and the need for reliability2008
- A Generalized Morphological Transform Based Faulty Feeder Selector Suitable for the Non-Effectively Grounded Power Systems2007
- Grounding Fault Protection with Phase Current Difference for Ineffectively Earthed Power Systems2006