Stability Improvement of Current Control by Voltage Feedforward Considering a Large Synchronous Inductance of a Diesel Generator
- 16 May 2018
- journal article
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Industry Applications
- Vol. 54 (5) , 5134-5142
Abstract
In this paper, the damping ability of point of common coupling (PCC) voltage feedforward is analyzed in order to improve the stability of current control, in which interference with an LCL filter of a battery energy storage system (BESS) and synchronous inductance of a diesel generator is considered in a stand-alone microgrid. A BESS can be charged by a diesel generator when the state of charge of the battery bank is significantly insufficient and where the BESS operates with constant current constant voltage control and the diesel generator provides constant voltage constant frequency control. In this case, large synchronous when the diesel generator is in a steady state may severely cause the instability of current control. The stability analysis should be required to guarantee the paralleled operation between BESS and diesel generator. An equivalent circuit model of the diesel generator is needed to perform these processes. To bring availability of analysis, this paper considers a simple equivalent circuit model considering synchronous inductance in the steady state, and it has very large inductance corresponding 1 per unit. The resonance issue is attenuated by the damping ability of PCC voltage feedforward where it is possible to improve the stability by appropriately adjusting the gain of the voltage feedforward. The effects of the synchronous inductance and the feedforward loop are analyzed in the s-domain and z-domain. The gain of the voltage feedforward is determined to be 0.2 and 0.4 based on stability analysis. To verify the validity of the damping effect of PCC voltage feedforward, a demonstration site is constructed and the stability is verified through simulation and experiment with a full model, and total harmonic distortion of current is improved to 2.44%.Keywords
Funding Information
- Ministry of Land, Infrastructure and Transport (18RTRP-B149104-01)
This publication has 19 references indexed in Scilit:
- A Two-Stage Model Predictive Control Strategy for Economic Diesel-PV-Battery Island Microgrid Operation in Rural AreasIEEE Transactions on Sustainable Energy, 2016
- Optimal Design of High-Order Passive-Damped Filters for Grid-Connected ApplicationsIEEE Transactions on Power Electronics, 2015
- Impedance Shaping of the Grid-Connected Inverter with LCL Filter to Improve Its Adaptability to the Weak Grid ConditionIEEE Transactions on Power Electronics, 2014
- Wide Damping Region for LCL-Type Grid-Connected Inverter With an Improved Capacitor-Current-Feedback MethodIEEE Transactions on Power Electronics, 2014
- Robust Single-Loop Direct Current Control of LCL-Filtered Converter-Based DG Units in Grid-Connected and Autonomous Microgrid ModesIEEE Transactions on Power Electronics, 2014
- Regions of Active Damping Control for LCL FiltersIEEE Transactions on Industry Applications, 2013
- Energy Management of Microgrid in Grid-Connected and Stand-Alone ModesIEEE Transactions on Power Systems, 2013
- Evaluations of current control in weak grid case for grid‐connected LCL‐filtered inverterIET Power Electronics, 2013
- Analysis of the Passive Damping Losses in LCL-Filter-Based Grid ConvertersIEEE Transactions on Power Electronics, 2012
- Full-Feedforward Schemes of Grid Voltages for a Three-Phase $LCL$-Type Grid-Connected InverterIEEE Transactions on Industrial Electronics, 2012