Fault current testing envelopes for VSC HVDC circuit breakers
Open Access
- 1 April 2016
- journal article
- conference paper
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 10 (6) , 1393-1400
Abstract
Circuit breakers for high voltage direct current (HVDC) applications are seen as a required technological step in the development of HVDC grids. The development of several new HVDC circuit breaker prototypes indicate that this step may be achieved in the years to come. In order to facilitate the installation of HVDC circuit breakers, appropriate standards and tests need to be developed. These tests and standards must ensure that the technology is capable of functioning as required. In cases where direct testing cannot be carried out, a synthetic test circuit is used to recreate the conditions of the power system. Testing envelopes which encapsulate the fault currents for two types of voltage source converter under fault conditions are analytically derived in this study and compared with simulations. Testing envelopes allow specifications for HVDC breaker test circuits to be defined. Discussion is also given to the worst type of fault and protection operation time estimates.Keywords
Funding Information
- National Grid (TAO/22360)
This publication has 15 references indexed in Scilit:
- Fault detection and Interruption in an earthed HVDC grid using ROCOV and hybrid DC breakers2015
- Architecture of Nan'ao multi-terminal VSC-HVDC system and its multi-functional controlCSEE Journal of Power and Energy Systems, 2015
- Defining the exact number of sub-module transitions in fundamental frequency modulated modular multilevel converters2015
- Determination of DC Short-Circuit Currents of MMC-HVDC Converters for DC Circuit Breaker Dimensioning2015
- Fault Current Testing Envelopes for VSC HVDC Circuit Breakers2015
- DC Transmission Grid With Low-Speed Protection Using Mechanical DC Circuit BreakersIEEE Transactions on Power Delivery, 2014
- Comparison of fault currents in multiterminal HVDC grids with different grounding schemes2014
- A Simplified Nearest Level Control (NLC) Voltage Balancing Method for Modular Multilevel Converter (MMC)IEEE Transactions on Power Electronics, 2014
- The Alternate Arm Converter: A New Hybrid Multilevel Converter With DC-Fault Blocking CapabilityIEEE Transactions on Power Delivery, 2013
- Contribution of HVDC converters to the DC short circuit current2013