Abstract
A common method for load sharing is using frequency and voltage droop controllers because there is no need to have communication links in the microgrid (MG). However, the droop control strategy has a drawback, that is, it imposes voltage and frequency deviations, which can be fixed by adding a secondary control loop. On the other hand, if the MG operates connected to the grid, a tertiary controller for regulating the injected power must be added. This paper proposes a multitask fuzzy secondary controller (FSC) applied to ac MGs acting only on the secondary control layer. The proposed controller allows stand-alone and grid-tied operations, regulating the voltage and frequency in the secondary and the active and reactive powers, simultaneously, without a tertiary controller. Stability analysis are presented showing that the FSC keeps the MG stable while operating within a proposed operation range. A MG simulation test bed based on power inverters is presented to validate the FSC operation and to compare to conventional hierarchical controller. The proposed FSC fixes the deviations in the same way as the conventional controller during the islanded operation tests and allows the MG to inject power into the grid.
Funding Information
  • Fundação de Amparo à Pesquisa do Estado de São Paulo (2016/25017-1)
  • Conselho Nacional de Desenvolvimento Científico e Tecnológico (233605/2014-2, 305892/2017-7)
  • Coordenação de Aperfeiçoamento de Pessoal de Nível Superior

This publication has 14 references indexed in Scilit: