Optimisation of a sensor for onsite detection of partial discharges in power transformers by the UHF method
Authors:
- 22 December 2008
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 15 (6) , 1634-1639
Abstract
Among the different solutions which allow onsite partial discharge measurement in energized power transformers, the UHF technique is gaining general interest. In order to apply this method in existing transformers, it is considered advantageous to design a UHF sensor to be fitted inside the transformer tank. This paper describes the constraints affecting the development of such sensor and the process followed to optimize its design. During this process, different solutions for broadband UHF antennas were analysed. The selection was based on computer simulation and experimental results. Computer simulation was used to evaluate differences in radiation pattern, antenna impedance, gain and effective area. Measurements of the antenna response to different partial discharge sources in oil were performed using an oil dielectric breakdown test set in an electromagnetic shielded laboratory. A group of selected antennas were then tested in a power transformer simulating the broadband signals generated by partial discharges by injecting controlled voltage pulses in the transformer. Finally, a sensor based on a conical monopole antenna structure was built and attached to a specially designed housing to be fitted inside the transformer tank through the drain valve. This final prototype was benchmarked during a high voltage factory test of a power transformer which showed a significant partial discharge activity.Keywords
This publication has 4 references indexed in Scilit:
- Sensitivity Check of Internal Sensor for Power Transformer Partial Discharge Measurements2006
- Partial discharge monitoring for power transformer using UHF sensors. Part 2: field experienceIEEE Electrical Insulation Magazine, 2005
- On line pd measurements and diagnosis on power transformersIEEE Transactions on Dielectrics and Electrical Insulation, 2005
- High-voltage onsite commissioning tests for gas-insulated substations using uhf partial discharge detectionIEEE Transactions on Power Delivery, 2003