Aging of Oil-Impregnated Paper High Voltage Current Transformers: Long Duration Test and Lifespan Estimation
- 2 October 2023
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 31 (1) , 358-365
Abstract
Although the current transformer (CT) is an essential component in the electrical power system and its failure may result in serious consequences, there are no accelerated aging tests for this equipment prescribed by technical standards. Life estimation for this equipment is generally made based on field experience, something that cannot be done for new models and/or new manufacturers. In this work, experimental results of life tests performed on mockups, representing high-voltage CTs with oil-impregnated paper insulation, are presented and discussed. The analysis is based on the application of a multistress model, which combines the Montsinger rule and inverse power law. The proposed approach considers the existence of threshold values for electrical and thermal stresses, below them, electrical and thermal degradation is negligible. An order of magnitude for the electrical stress threshold value ( ${E}_{{0}}$ ) and for the electrical aging exponent ( ${n}$ ) is obtained from the application of the test results to the model used in this investigation.Keywords
Funding Information
- GE Vernova
This publication has 7 references indexed in Scilit:
- Temperature Effect on Electrical Aging Model for Field-Aged Oil Impregnated Paper Insulation2022
- Research on Deterioration Mechanism of Oil-paper Insulation of 220 kV Current Transformer2021
- Instrument transformers2018
- A general multi-stress life model for insulating materials with or without evidence for thresholdsIEEE Transactions on Electrical Insulation, 1993
- Models for insulation aging under electrical and thermal multistressIEEE Transactions on Electrical Insulation, 1990
- General Equation of the Decline in the Electric Strength for Combined Thermal and Electrical StressesIEEE Transactions on Electrical Insulation, 1984
- Effect of load factor on operation of power transformers by temperatureElectrical Engineering, 1940