Determination of the true water content, the nature of the impurities and their concentration in transformer oil
Authors:
Open Access
- 1 January 2019
- conference paper
- Published by EDP Sciences in E3S Web of Conferences
- Vol. 124, 05005
Abstract
During the operation of transformers, the insulating oil is aging, therefore, there is the deterioration of its insulating properties, which is determined by multiple physico-chemical processes. The most dangerous factor, from the point of view of preserving the operational reliability and resource of a power transformer, is the moisture content of the insulation. Most methods for determining moisture content have measurement errors. These errors are largely dependent on impurities that are contained in the oil. The modified Fisher method proposed in the article allows determining the amount of impurities in the oil and the absolute moisture content. Conducted research allows also to determine the composition of impurities, to reveal the relationship between impurities and some parameters of transformer oil.Keywords
This publication has 4 references indexed in Scilit:
- Investigation of transformer oil by nuclear magnetic relaxation and Z-scanningChemistry and Technology of Fuels and Oils, 2013
- Bias Assessment of Current Technologies Used for the Determination of Low Levels of Moisture in Mineral Oil SamplesAnalytical Chemistry, 2001
- Effect of Hydrocarbon Composition on the Measurement of Water in Oils by Coulometric and Volumetric Karl Fischer MethodsAnalytical Chemistry, 1998