Local Identification of Voltage Emergency Situations
Authors:
- Thierry Van CutsemTCThierry Van Cutsem
- 9 July 2008
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Systems
- Vol. 23 (3) , 1239-1248
Abstract
This paper proposes a simple procedure to identify the onset of long-term voltage instability from the time evolution of the distribution voltages controlled by load tap changers. The moving average of sampled measurements is computed and used to trigger local emergency signals. The method is validated on voltage signals obtained from time simulation of a realistic test system. The ability to identify instability in the critical area is demonstrated in three test cases.Keywords
This publication has 12 references indexed in Scilit:
- Tracking maximum loadability conditions in power systems2007
- Undervoltage load shedding improving security as reasonable measure for extreme contingencies2005
- Unified Sensitivity Analysis of Unstable or Low Voltages Caused by Load Increases or ContingenciesIEEE Transactions on Power Systems, 2005
- Voltage-stability protection and control using a wide-area network of phasor measurementsIEEE Transactions on Power Systems, 2003
- Voltage Stability of Electric Power Systems1998
- Interaction among multiple controls in tap change under load transformersIEEE Transactions on Power Systems, 1997
- Concepts of undervoltage load shedding for voltage stabilityIEEE Transactions on Power Delivery, 1992
- Voltage stability evaluation using modal analysisIEEE Transactions on Power Systems, 1992
- Reverse action of on-load tap changer in association with voltage collapseIEEE Transactions on Power Systems, 1991
- Discrete Models of Slow Voltage Dynamics for under Load Tap-Changing Transformer CoordinationIEEE Transactions on Power Systems, 1987