A Novel Method for Fault Location of Transmission Lines by Wide-Area Voltage Measurements Considering Measurement Errors
Authors:
- 5 December 2014
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Smart Grid
- Vol. 6 (2) , 874-884
Abstract
Smart transmission grids are intended to utilize various measurements for enhanced operation. In particular, synchronized phasor measurements have found many applications in this context. This paper presents a linear weighted least-squares (WLS) method for fault location estimation of transmission lines by synchronized voltage measurements. The measurements may be taken from the faulted line terminals or buses far from the faulted line. The circuit equations of the network are used to find the transfer function between the fault location and each voltage measurement. Next, two auxiliary variables are defined to transform the nonlinear fault location estimation problem into a linear WLS problem. A closed-form solution is then obtained for fault location. The use of multiple measurements provides the opportunity of identifying erroneous measurements by a statistical test. The linearity of the problem expedites both estimation and identification procedures. Moreover, the method requires neither to classify the fault type nor to estimate the fault resistance. Furthermore, transmission lines are modeled by distributed parameters so that the method can be applicable to long lines. Electromagnetic transient simulations for 9-bus and 22-bus test systems reveal accurate fault location estimation, regardless of fault type and resistance, as well as successful identification of measurement errors.Keywords
This publication has 33 references indexed in Scilit:
- A Straightforward Method for Wide-Area Fault Location on Transmission NetworksIEEE Transactions on Power Delivery, 2014
- A Simple Synchrophasor Estimation Algorithm Considering IEEE Standard C37.118.1-2011 and Protection RequirementsIEEE Transactions on Instrumentation and Measurement, 2013
- P and M Class Phasor Measurement Unit Algorithms Using Adaptive Cascaded FiltersIEEE Transactions on Power Delivery, 2013
- Optimal Integration of Phasor Measurement Units in Power Systems Considering Conventional MeasurementsIEEE Transactions on Smart Grid, 2012
- Optimal PMU Placement by an Equivalent Linear Formulation for Exhaustive SearchIEEE Transactions on Smart Grid, 2012
- A Fault Location Technique for Two-Terminal Multisection Compound Transmission Lines Using Synchronized Phasor MeasurementsIEEE Transactions on Smart Grid, 2011
- An Adaptive Dynamic Phasor Estimator Considering DC Offset for PMU ApplicationsIEEE Transactions on Power Delivery, 2011
- Development of a new fault location system for multi-terminal single transmission linesIEEE Transactions on Power Delivery, 1995
- A practical approach to accurate fault location on extra high voltage teed feedersIEEE Transactions on Power Delivery, 1993
- A new fault location technique for two- and three-terminal linesIEEE Transactions on Power Delivery, 1992