Proposed diagnostic methodology using the cross‐correlation coefficient factor technique for power transformer fault identification
Authors:
Open Access
- 1 March 2017
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Electric Power Applications
- Vol. 11 (3) , 412-422
Abstract
This study investigates the impact of electrical parameter variation of a high‐frequency transformer model on its sweep frequency response analysis (SFRA) signature to help in classification and interpretation. The simulations have been done using MATLAB and compared with the reference data. The results of SFRA measurements are repeatable up to and beyond 1MHz. The proposed diagnostic methodology using the Cross‐Correlation Coefficient Factor (CCF) is used to identify the transformer faults. CCF used to measure the degree of relationship between two variables that establish a relation between the predicted and actual data set. The results of this proposed methodology using the CCF compared with existing Chinese Standard factor (CSF) indicate that, the proposed method is valid to identify the transformer faults. Characteristics of the proposed scheme are fully analyzed by extensive MATLAB simulation studies that clearly reveal that this method can accurately identify the transformer faults compared with CSF. And also does not affected by different fault conditions such as transformer normal condition, Turn to Turn Fault for both HV, LV sides, Axial Fault and/or Radial Faults on both sides, Short Circuit Fault between H.V and L.V Sides, Short Circuit to Ground Fault for both HV, LV sides.Keywords
This publication has 23 references indexed in Scilit:
- Investigation of the transformer winding high‐frequency parameters identification using particle swarm optimisation methodIET Electric Power Applications, 2016
- Examining the ageing of transformer insulation using FRA and FDS techniquesIEEE Transactions on Dielectrics and Electrical Insulation, 2015
- ANN and cross-correlation based features for discrimination between electrical and mechanical defects and their localization in transformer windingIEEE Transactions on Dielectrics and Electrical Insulation, 2014
- Statistical evaluation of a new technique for Sweep Frequency Response Analysis2012
- A new technique for a better sweep frequency response analysis interpretation2012
- FRA vs. short circuit impedance measurement in detection of mechanical defects within large power transformer2012
- A Novel Online Technique to Detect Power Transformer Winding FaultsIEEE Transactions on Power Delivery, 2012
- Robust transfer function identification via an enhanced magnitude vector fitting algorithmIET Control Theory & Applications, 2010
- Sweep frequency response analysis (SFRA) for the assessment of winding displacements and deformation in power transformersElectric Power Systems Research, 2008
- Diagnosing transformer faults using frequency response analysisIEEE Electrical Insulation Magazine, 2003