Hysteresis controller in modified PMSG wind-PV systems for power quality enhancement in grid

Authors:

Abstract
The scheme has both the generator side converter and grid side converter to inject wind and PV power into the grid. Hysteresis controller is connected in order to enhance power quality of the Permanent magnet synchronous generator (PMSG) connected wind system. One of the greatest assets of the PMSG is that the output power is sinusoidal as per the grid requirement. There is no exchange of reactive power between the PMSG and generator side PEC during normal operation, it only absorbs electric power. This reduces the generator (stator) current during the normal operation. In MPPT controlled PV system, perturbation and observe method is used. Perturbing the duty cycle of the power converter implies modifying the operating voltage of the DC link which is connected between PV array and the power converter. In various conditions the output is compared and discussed. The hysteresis controller in modified PMSG wind-PV energy systems for power quality enhancement in grid is simulated using MATLAB-2009b/SIMULINK in simpower systems and simscape blockset.

This publication has 15 references indexed in Scilit: