Effect of Aging Degree on Partial Discharge Degradation of Oil-paper Insulation
Authors:
- 1 December 2021
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 28 (6) , 2099-2107
Abstract
This study conducts thermal aging treatment to study the effect of thermal aging on the PD degradation process of the oil-paper insulation. The partial discharge inception voltages, extinction voltages, carbon mark, and microscopic morphology of samples are analyzed. The results show that thermal aging does not reduce the partial discharge inception voltages of oil-paper but can make the spark produced in the oil-paper more difficult to extinguish. At the initial stage, thermal aging has little effect on the development of partial discharge in normal direction of samples, while in later stages, the effect begins to appear; thermal aging reduces the insulation performance between layers of oil impregnated paper and accelerates the carbon trace growth rate in the horizontal direction. In this model, the first layer is most severely bombarded by electrons, and this layer is most obviously affected by the electric field in the normal direction at the contact point between the electrode and the insulating paper. The lower layer is affected by the horizontal and vertical electric fields; therefore, a large area of fiber looseness occurs on the surface of the oil impregnated paper. The degree of deterioration is proportional to the endurance time and aging time, and the damage degree of oil impregnated paper decreases with the increase of the number of layers.Keywords
This publication has 14 references indexed in Scilit:
- Dielectric properties of epoxy resin impregnated paper insulation in different stages of partial discharge developmentPolymer Composites, 2019
- Partial discharge damage mechanisms in laminated oil-paper insulationCellulose, 2019
- The microscopic morphology of insulation pressboard: an image processing perspectiveCellulose, 2018
- FDS analysis for multilayer insulation paper with different aging status in traction transformer of high-speed railwayIEEE Transactions on Dielectrics and Electrical Insulation, 2017
- Investigations on the air-gap partial discharge inception characteristics of vegetable oil-paper insulation system2017
- A study of oil-impregnated paper insulation aged with thermal-electrical stress: PD characteristics and trap parametersIEEE Transactions on Dielectrics and Electrical Insulation, 2016
- Evolution of pd patterns in polyethylene insulation cavities under AC voltageIEEE Transactions on Dielectrics and Electrical Insulation, 2012
- Applicability of methanol as new marker for paper degradation in power transformersIEEE Transactions on Dielectrics and Electrical Insulation, 2011
- Degradation of cellulosic insulationin power transformers.Part 3: Effects of oxygen and water on ageing in oilIEE Proceedings - Science, Measurement and Technology, 2000
- Review of chemical indicators of degradation of cellulosic electrical paper insulation in oil-filled transformersIEE Proceedings - Science, Measurement and Technology, 1994