Construction and Commissioning of the KSTAR Helium Distribution System
- 12 May 2009
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Applied Superconductivity
- Vol. 19 (3) , 1582-1586
Abstract
The KSTAR components requiring cryogenic helium coolant for superconducting magnet operations are connected to the helium refrigeration system (HRS) through the helium distribution system (HDS), the final helium distribution station. Twenty eight cryogenic valves including 4 quench protecting valves, many sensors such as temperature sensors, pressure transmitters, and flowmeters are mounted on the system. The HDS has to control the 4.5 K supercritical helium (600 g/s) for 30 superconducting coils and their superconducting bus-lines, 55 K helium (270 g/s) pressurized to 18 bars for the thermal shields and the gravity supports, and a maximum 17.5 g/s of liquid helium for 18 current leads, provided from the HRS which has a 4.5 K equivalent cooling power of 9 kW. The helium distribution system consists of a helium distribution box (DB), 5 helium transfer lines, a PLC based helium control system (HCS), etc. The helium control system is connected to the KSTAR supervisory control & interlock system. The detailed status regarding the construction, commissioning during first cool-down, and the instrumentation & control (I&C) system are included in this paper.Keywords
This publication has 7 references indexed in Scilit:
- The ITER toroidal field model coil projectFusion Engineering and Design, 2005
- Superconducting CICC for SST-1 tokamak magnets2002
- Comparative analysis of design options for current leads for Wendelstein 7-X magnet systemIEEE Transactions on Applied Superconductivity, 2002
- Design and construction of the KSTAR tokamakNuclear Fusion, 2001
- The ITER challengeFusion Engineering and Design, 1993
- Cryogenic Process Engineering1989
- Materials at Low Temperatures1983