Abstract
This paper investigates characterization of low-frequency electromagnetic transients occurring in power networks with the Stockwell transform (S-transform). Three characteristic cases of real network events are considered. The experiments are conducted in the 35 kV network, and voltage and current signals are recorded. The S-transform is applied to analyze voltage and current signals recorded during earth fault, ferroresonance and transformer inrush. The obtained results demonstrate that application of the S-transform enables identifying and distinguishing different low-frequency electromagnetic transients. The S-transform scalograms and energy spectrum diagrams provide necessary information to enable more efficient protection measures against problems in the network caused by different low-frequency electromagnetic transient phenomena.
Funding Information
  • Ministry of Science, Higher Education and Youth of Canton Sarajevo. (27-02-35-18976-3.1/23)

This publication has 22 references indexed in Scilit: