Aiming at the problem that leakage protection cannot be put into operation in the LV TN-C-S systems, due to the large inherent residual current, this paper proposes a leakage protection method using both the residual and the unbalance current, RUM. The quantitative relationship between the residual current, the unbalance current and the fault current is derived. It is proved that the ratio of the residual current vector and the unbalanced current vector is a complex constant when there are no faults in the system. After the complex constant is calculated with the mutation vectors of the unbalanced and residual current when no faults exist in the system, fault current can be estimated and monitored. Experiment results show that the detection sensitivity at the outlet of the transformer can be 0.1 A, which satisfies the requirement of leakage protection.