Exploring aeration-associated energy savings at a conventional water reclamation plant
Authors:
- 3 July 2017
- journal article
- Published by IWA Publishing in Water Science & Technology
- Vol. 76 (8) , 2222-2231
Abstract
Aeration accounts for a large fraction of energy consumption at conventional water reclamation plants (WRPs). Older plants were designed when control techniques were relatively primitive and energy consumption was less of a concern. As a result, although process operations at older WRPs can satisfy effluent permit requirements, they can operate with excess aeration. In this study, we developed a wastewater process model to evaluate possible aeration savings at the Metropolitan Water Reclamation District of Greater Chicago Calumet WRP, one of the oldest plants in Chicago. Based on subsets of influent characteristics, we identified eight steady-state scenarios. We also identified transient scenarios that included high probability perturbations and more challenging but lower probability conditions. Results indicate that the Calumet WRP frequently operates with excess aeration. Effluent dissolved oxygen is the limiting parameter with respect to aeration saving and permit requirements. In a typical storm event, aeration could be reduced by up to 50%; even under low probability challenging perturbations, aeration can be decreased by 35% from current average levels and all permit requirements can be satisfied. Annual cost savings from cutting the aeration by 35% could be more than $1.2 million.Keywords
This publication has 12 references indexed in Scilit:
- Reducing aeration energy consumption in a large-scale membrane bioreactor: Process simulation and engineering applicationWater Research, 2016
- Wastewater treatment process impact on energy savings and greenhouse gas emissionsWater Science & Technology, 2014
- Modification of oxygen transfer rates in activated sludge with its characteristic changes by the addition of organic polyelectrolyteChemical Engineering Journal, 2013
- Improving Nutrient Removal While Reducing Energy Use at Three Swiss WWTPs Using Advanced ControlWater Environment Research, 2012
- Reduction of aeration costs by tuning a multi-set point on/off controller: A case studyControl Engineering Practice, 2011
- Oxygen transfer in activated sludge – new insights and potentials for cost savingWater Science & Technology, 2011
- Energy saving in activated sludge plants by the use of more efficient fine bubble diffusersWater and Environment Journal, 2010
- Real‐Time Aeration Efficiency Monitoring in the Activated Sludge Process and Methods to Reduce Energy Consumption and Operating CostsWater Environment Research, 2009
- Nitrification and Denitrification in the Activated Sludge Process2002
- Applying fine bubble aeration to small aeration tanksWater Science & Technology, 2001