Measurement System for Current Transformer Calibration from 50 Hz to 150 kHz Using a Wideband Power Analyzer
Open Access
Abstract
Accurate and reliable characterization of current transformer (CT) performance is essential for maintaining grid stability and power quality in modern electrical networks. CT measurements are key to effective monitoring of harmonic distortions, supporting regulatory compliance and ensuring the safe operation of the grid. This paper addresses a method for the characterization of CTs across an extended frequency range from 50 Hz up to 150 kHz, driven by increasing power quality issues introduced by renewable energy installations and non-linear loads. Traditional CT calibration approaches involve measurement setups that offer ppm-level uncertainty but are complex to operate and limited in practical frequency range. To simplify and expand calibration capabilities, a calibration system employing a sampling ammeter (power analyzer) was developed, enabling the direct measurement of CT secondary currents of an unknown CT and a reference CT without any further auxiliary equipment. The resulting expanded magnitude ratio uncertainties for the wideband CT calibration system are 10 ppm () up to 10 kHz and less than 120 ppm from 10 kHz to 150 kHz; these uncertainties do not include the uncertainty of the reference CT. Additionally, the operational conditions and setup design choices, such as instrument warm-up duration, grounding methods, measurement shunt selection, and cable type, were evaluated for their impact on measurement uncertainty and repeatability. The results highlight the significance of minimizing parasitic impedances at higher frequencies and maintaining consistent testing conditions. The developed calibration setup provides a robust foundation for future standardization efforts and practical guidance to characterize CT performance in the increasingly important supraharmonic frequency range.
Keywords
Funding Information
- European Partnership on Metrology (22NRM06)
This publication has 44 references indexed in Scilit:
- Flexible Generation Architecture for Current Transformers Testing up to 150 kHz2024
- Characterization of MV Instrument Transformers for Power Quality Measurement: the contribution from the IT4PQ project2024
- Reference Measurement Systems for the Calibration of Instrument Transformers Under Power Quality Phenomena and their Uncertainties2023
- Diagnosis of supraharmonics-related problems based on the effects on electrical equipmentElectric Power Systems Research, 2021
- Impact of high-frequency harmonics (0–9 kHz) generated by grid-connected inverters on distribution transformersInternational Journal of Electrical Power & Energy Systems, 2020
- Calibration of Current Transformers in distorted conditionsJournal of Physics: Conference Series, 2018
- High Voltage CT Ratio Errors Dependency on Voltage and Power Factor of the Metered Load2018
- Review of harmonic analysis, modeling and mitigation techniquesRenewable and Sustainable Energy Reviews, 2017
- A survey of current shunts for ac power measurements2010
- Sinusoidal response of coaxial current shuntsProceedings of the Institution of Electrical Engineers, 1977