This paper presents a new modeling framework to carry out system-wide dynamic studies of DFIG-based wind farms embedded in multi-terminal VSC-HVDC power grids. Contrary to existing approaches using electromagnetic transient (EMT) solutions, this is an RMS-type formulation which maintains a high-degree of fidelity while enabling much faster steady-state and dynamic simulations. The new modeling framework includes AC/DC power grids of an arbitrary size, topology and number of offshore VSC-connected wind farms. This has required the development of the RMS model of a DFIG with explicit representation of all the dynamic effects relevant for dynamic problems of the electromechanical type. All the control functions and parameters of the rotor-side converter, the grid-side converter and the DC link, are accounted for in the new DFIG model. The prowess of the new formulation is demonstrated using a six-terminal VSC-HVDC link with two VSC-connected 200-MW wind farms. The impact of the wind farms' operation on the DC grid and the AC grids is assessed. The fidelity of the output results is compared against those of the EMT-type model implemented in Simscape Electrical of Simulink. The study shows that they favorably compare with each other, with differences inferior to 3%. The computational efficiency of the new dynamic modeling framework for HVDC-connected wind farms is unassailable.
Funding Information
  • National Autonomous University of Mexico

This publication has 21 references indexed in Scilit: