Parameter Determination and Ion Current Improvement of the Ion Current Sensor Used for Flame Monitoring
Open Access
Abstract
Flame monitoring of industrial combustors with high-reliability sensors is essential to operation security and performance. An ion current flame sensor with a simple structure has great potential to be widely used, but a weak ion current is the critical defect to its reliability. In this study, parameters of the ion current sensor used for monitoring flames on a Bunsen burner are suggested, and a method of further improving the ion current is proposed. Effects of the parameters, including the excitation voltage, electrode area, and electrode radial and vertical positions on the ion current, were investigated. The ion current grew linearly with the excitation voltage. Given that the electrodes were in contact with the flame fronts, the ion current increased with the contact area of the cathode but independent of the contact area of the anode. The smaller electrode radial position resulted in a higher ion current. The ion current was insensitive to the anode vertical position but largely sensitive to the cathode vertical position. Based on the above ion current regularities, the sensor parameters were suggested as follows: The burner served as a cathode and the platinum wire acted as an anode. The excitation voltage, anode radial and vertical positions were 120 V, 0 mm, and 6 mm, respectively. The method of further improving the ion current by adding multiple sheet cathodes near the burner exit was proposed and verified. The results show that the ion current sensor with the suggested parameters could correctly identify the flame state, including the ignition, combustion, and extinction, and the proposed method could significantly improve the magnitude of the ion current.Keywords
This publication has 28 references indexed in Scilit:
- Lean blowout detection for bluff-body stabilized flameFuel, 2020
- Combustion state monitoring of premixed heating appliances with flame ionization current and chemiluminescenceCombustion Science and Technology, 2018
- Flame monitoring of a model swirl injector using 1D tunable diode laser absorption spectroscopy tomographyMeasurement Science and Technology, 2017
- Study on ignition and flame development in gasoline partially premixed combustion using multiple optical diagnosticsCombustion and Flame, 2017
- Ion current sensing-based lean blowout detection for a pulse combustorCombustion and Flame, 2017
- Ignition behaviors of pulverized coal particles in O2/N2 and O2/H2O mixtures in a drop tube furnace using flame monitoring techniquesProceedings of the Combustion Institute, 2015
- Simultaneous time-resolved fluctuating temperature and acoustic pressure field measurements in a premixed swirl flameApplied Energy, 2014
- The John Zink Hamworthy Combustion Handbook2013
- Diagnostic techniques for the monitoring and control of practical flamesProgress in Energy and Combustion Science, 2010
- Combustion control and sensors: a reviewProgress in Energy and Combustion Science, 2002