Abstract
In this article, a utility-current feedforward-based control method for an active power filter is proposed. The DC voltage of the power converter is detected and sent to a feedback control circuit to generate a regulating signal for DC voltage regulation, while the utility current is detected and sent to a multiplier to be multiplied by the regulating signal to directly obtain the modulation signal of the pulse-width modulation circuit. Hence, the proposed control method detects only the utility current and DC voltage of the power converter. Compared with the conventional control method, the proposed approach requires no reference signal to be calculated, so detection of the utility voltage can be omitted and the control circuit can thus be simplified. To demonstrate the performance of the proposed control method, a prototype is developed and tested. Experimental results validate that the proposed control method for an active power filter can achieve the expected performance.

This publication has 10 references indexed in Scilit: