Abstract
In DC grids, multiple DC circuit breakers (DCCBs) on a DC bus can be replaced by a multiport DCCB (MDCCB) to reduce the investment cost. However, compared with a single DCCB, the MDCCB contains more branches and has a greater probability of branch unavailability; furthermore, its interruption failure caused by branch unavailability leads to more severe consequences. A few studies avoid the interruption failure caused by ultrafast disconnector (UFD) failure, but the interruption failure caused by the semiconductor branch unavailability is rarely considered. This article proposes a novel MDCCB with N-1 security ability, which is applicable for different numbers of ports and can interrupt faults even when any internal branch is unavailable. The working principles under normal condition and branch unavailability conditions are presented. The fault currents of DC grids are calculated to design the parameters of MDCCB. The feasibility of the proposed topology is validated by a small-scale prototype, and the working performance is further validated by simulations in the DC grid. Compared with existing MDCCBs, the proposed MDCCB combines the characteristics of low investment cost and high reliability, which can ensure the safety and economy of DC grids.
Funding Information
  • National Natural Science Foundation of China (52107130)

This publication has 37 references indexed in Scilit: