Cooling Tower Water Conditioning Study
Author:
- M. F. HumphreyMHM. F. Humphrey
Open Access
- 1 January 1981
- journal article
- research article
- Published by Taylor & Francis in Ozone: Science & Engineering
- Vol. 3 (2) , 109-119
Abstract
Successful elimination of cooling tower treatment chemicals has been accomplished at JPL. Three towers have functioned for long periods of time with ozone as the only treatment for the water. The water in the systems has been reused as much as thirty (30) times (cycles of concentration) without deleterious effects to the heat exchangers. Actual system blow–down was eliminated and the only makeup water added was that required to replace the evaporation and mist entrainment losses. Minimum water savings alone were approximately 75.1 1/kg/year (18,000 gal/ton/year). Cost estimates indicate that a savings of 55 percent was obtained on the JPL systems using ozone. [This amounts to a cost savings of approximately $O.024/kg/yr (22.00/ton/year) including labor.] A major problem experienced in the use of ozone for cooling tower ap–lications was the difficulty of accurate concentration measurements. The ability to control the operational characteristics relies on easily and accurately determined concentration levels.Keywords