Abstract
This paper investigates improvement of under voltage ride-through capability of a variable speed drive to short-term power interruptions by use of switched capacitors. Variable speed drives are sensitive to voltage dips. Voltage dip related trips can lead to loss of key processes. To support the grid in South Africa, the transmission operator requires that power station equipment withstand certain voltage dips. Simulation and experimental results demonstrate feasibility of the proposed solution. Simulation results show a torque ripple of 16% and 25% during voltage dip initiation and clearance respectively. Minor speed disturbances are observed at both instances. Inrush charging currents are observed at both ride-through module activation and dip clearance as the variable speed drive capacitor charges up. Minimization of capacitor charging inrush currents to avoid damage to VSD components through the use of resistive elements is explored. The proposed solution can be extended to super/ultra-capacitors and batteries with little or no hardware modifications.