Effect of space charge on breakdown characteristics of aged oil-paper insulation under DC voltage
Authors:
- 14 November 2016
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 23 (5) , 3143-3150
Abstract
Due to its excellent performance, oil-paper insulation has been widely used in many power apparatuses including converter transformer of high voltage direct current (HVDC) system. Space charge accumulation phenomena may significantly distort local electric field inside transformer and cause oil-paper insulation overstressing. As a result of long term operation, oil-paper gradually degrades. In most severe cases, the breakdown of insulation system may occur. In this work, the effect of space charge on breakdown characteristics of aged oil-paper insulation is investigated. Oil-paper samples with different aging states are obtained by thermally accelerated aging for various periods of time, categorized by the degree of polymerization (DP) of 1107 (new), 725, 504, 376 and 241, respectively. Experimental results show that the breakdown voltage of oil-paper samples without pre-stressing remains almost constant with thermal degradation. After the homo-polarity pre-stress, when the DP value is higher than ~300 (from 1107 to 376), the breakdown voltage has an increasing tendency with an increase in thermal degradation. On the contrary, the breakdown voltage presents a decreasing tendency after the hetero-polarity pre-stress. When the DP is lower than ~300 (DP241), the changes of breakdown voltage does not remain the same trend as previous samples after pre-stressing. Meanwhile, space charge distributions in different aged samples are measured by the pulsed electro-acoustic (PEA) method, and the trap parameters are correspondingly evaluated. It has been experimentally demonstrated that special attention should be paid to space charge accumulation and aging state of oil-paper insulation, which may lead to severe insulation accidents.Keywords
This publication has 23 references indexed in Scilit:
- Space charge in polymeric insulation under ac electric fields A schematic model2013
- Identification of electron and hole trap based on isothermal surface potential decay modelJournal of Applied Physics, 2013
- Effects of paper-aged state on space charge characteristics in oil-impregnated paper insulationIEEE Transactions on Dielectrics and Electrical Insulation, 2012
- Time-to-breakdown and breakdown voltage for oil-impregnated insulation subjected to thermal aging2012
- Effect of nanoparticles on charge transport in nanofluid-impregnated pressboardJournal of Applied Physics, 2012
- Space charge dynamics in LDPE films immediately before breakdownIEEE Transactions on Dielectrics and Electrical Insulation, 2001
- The role of trapped space charges in the electrical aging of insulating materialsIEEE Transactions on Dielectrics and Electrical Insulation, 1997
- Space charge measurement techniques and space charge in polyethyleneIEEE Transactions on Dielectrics and Electrical Insulation, 1994
- Review of chemical indicators of degradation of cellulosic electrical paper insulation in oil-filled transformersIEE Proceedings - Science, Measurement and Technology, 1994
- Kinetics and mechanisms of the low-temperature degradation of celluloseCellulose, 1994