Second-Law Analysis to Improve the Energy Efficiency of Screw Liquid Chillers
Open Access
Abstract
This work applies the second-law analysis of thermodynamics to quantify the exergy destruction of the components of screw liquid chiller, and to identify the potential for each component to contribute to improve the overall energy efficiency of the system. Three screw liquid chiller units were built to demonstrate the feasibility of the model presented herein. Unit A was a 100 RT water-cooled screw liquid chiller. Unit B was modified from Unit A by switching the old condenser for a new one with a greater heat transfer, and Unit C was modified from Unit B by exchanging the compressor for a more efficient one. The results indicate that the compressor has the largest potential to improve energy efficiency, followed in order by the condenser, and then the evaporator. The second law analysis may help engineers to focus on the components with higher exergy destruction and quantify the extent to which modifying such components can influence, favorably or unfavorably, the performance of other components of the screw liquid chiller.Keywords
This publication has 10 references indexed in Scilit:
- Energy and exergy analysis of a ground-coupled heat pump system with two horizontal ground heat exchangersBuilding and Environment, 2007
- Experimental performance analysis of a solar assisted ground-source heat pump greenhouse heating systemEnergy and Buildings, 2005
- Exergy analysis of vapor compression refrigeration systemsExergy, An International Journal, 2002
- Exergy analysis and experimental study of heat pump systemsExergy, An International Journal, 2002
- Thermodynamic analysis of a lithium bromide/water absorption system for cooling and heating applicationsInternational Journal of Energy Research, 2001
- Thermoeconomic analysis of sensible heat, thermal energy storage systemsApplied Thermal Engineering, 1998
- On second-law analysis and the failed promise of finite-time thermodynamicsEnergy, 1998
- Second-law-based thermodynamic analysis of two-stage and mechanical-subcooling refrigeration cyclesInternational Journal of Refrigeration, 1996
- An exergy method for compressor performance analysisInternational Journal of Refrigeration, 1995
- Irreversibility analysis of a water-to-water mechanical-compression heat pumpEnergy, 1991