Abstract
This paper describes an specific approach to resolving problem of load frequency (LF) control in the power system of Montenegro ( Serbia and Montenegro). The complete LF controller was developed, coded, and implemented on the single PC computer ‘from the zero’ by the Company's staff in a fast, feasible, and cost‐effective manner. Its extremely high ‘in‐field’ efficiency was achieved by: the compact design of the controller, the implementation of the algorithm for efficient filtering of Control Error, the implementation of the algorithm for minimizing of the regulating units movement, as well as the feed‐back algorithm for permanent adjustment of the tie‐lines power measurements. All details on these algorithms are given. The official field results for the 6 month exploitation have confirmed the top regulating success in the Second UCTE Synchronous Zone. The Electric Power Company of Montenegro (EPCG) was recently subjected to enacting of the new Energy Law, and to the promoting of the free electricity market. So, the additional modifications were made at the AGC controller to meet the requirements of deregulation processes. Thus, the AGC system keeps track of the momentary active power imbalance, detects it, corrects it and communicates an adequate amount of the balance energy service (BES) power, on the 15‐minute basis, to the real‐time part of the market operating system (MOS), where it will be allocated to the real time market (RTM) balancing resources. Copyright © 2006 John Wiley & Sons, Ltd.