Abstract
Wind power ramping events refer to sustained unidirectional and large-magnitude fluctuations in wind power output over short durations, exhibiting distinct temporal characteristics and imposing significant impacts on power balance. To address the strong temporal dependency of wind power ramping events, a time-sequential outage model for conventional generators was derived and system operational states were sampled using non-sequential Monte Carlo simulation. Considering the frequency dynamics caused by active power imbalances, dynamic frequency security constraints were formulated. An optimal power flow model was developed to minimize wind curtailment and load shedding comprehensive losses, incorporating these dynamic frequency constraints. The optimal power flow model was employed to solve line power flows for sampled system states and compute comprehensive loss risk indices. Case studies on the IEEE RTS-79 system evaluated and compared operational risks across multiple scenarios, validating the effectiveness of the proposed methodology.
Funding Information
  • Chongqing Municipal Science and Technology Bureau Projects (CSTB2024TIAD-KPX0088)

This publication has 18 references indexed in Scilit: