Abstract
Practical subsynchronous instability events have been observed in doubly fed induction generator‐based wind farms, which are radially connected to fixed series compensated transmission lines. As a special type of subsynchronous resonance, this phenomenon is described here as subsynchronous control interaction (SSCI). This study proposes a centralised SSCI mitigation scheme named as subsynchronous damper (SSD). In this scheme, an additional high‐power electronic voltage‐sourced converter is added to the collection bus of wind farms. It is designed to dissipate the electrical resonance power of SSCI. Thus, SSD provides positive damping for SSCI. Its basic principle is explained with equivalent electric circuit and the sufficient conditions for stabilisation are obtained mathematically. Controller design guidelines are given and have been verified first by eigenvalue analysis. Then a method to choose the capacity of power electronic converter is proposed. The effectiveness of SSD is finally demonstrated by extensive time‐domain simulations on a target system.Keywords
Funding Information
- Beijing Institute of Technology Research Fund Program for Young Scholars
- National Natural Science Foundation of China (51322701)
This publication has 21 references indexed in Scilit:
- Investigation of SSR in Practical DFIG-Based Wind Farms Connected to a Series-Compensated Power SystemIEEE Transactions on Power Systems, 2014
- Coordinated Control of Wind Energy Conversion Systems for Mitigating Subsynchronous Interaction in DFIG-Based Wind FarmsIEEE Transactions on Smart Grid, 2014
- Sub-Synchronous Interaction Damping Control for DFIG Wind TurbinesIEEE Transactions on Power Systems, 2014
- SSR Alleviation by STATCOM in Induction-Generator-Based Wind Farm Connected to Series Compensated LineIEEE Transactions on Sustainable Energy, 2014
- Development and Field Experiments of a Generator Terminal Subsynchronous DamperIEEE Transactions on Power Electronics, 2014
- Reactance Scan Crossover-Based Approach for Investigating SSCI Concerns for DFIG-Based Wind TurbinesIEEE Transactions on Power Delivery, 2013
- Sub-Synchronous Control Interaction studies between full-converter wind turbines and series-compensated AC transmission lines2012
- Application of an SVC to damp sub-synchronous interaction between wind farms and series compensated transmission lines2012
- Modal Analysis of a DFIG-Based Wind Farm Interfaced With a Series Compensated NetworkIEEE Transactions on Energy Conversion, 2011
- Sub-synchronous control interactions between type 3 wind turbines and series compensated AC transmission systems2011