Discussion on Worst Distance Between SPD and Protected Device
Authors:
- 1 November 2011
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Electromagnetic Compatibility
- Vol. 53 (4) , 1081-1083
Abstract
It is commonly known that the longer the distance between a surge protective device (SPD) and a protected device, the worse the protection effectiveness. However, we observed there exists a worst distance between an SPD and a protected device in a low-voltage circuit. If a protected device and an SPD are separated by this worst distance, the protected device will be subject to the most severe surge voltage. The main reason for this phenomenon is that there usually exist two reflection processes, namely, that between the transformer and the SPD and that between the SPD and the protected device. These two refection processes lead to the superposition of voltage wave in a way that is different from that in the high-voltage circuit. This paper presents an analytical formula to estimate this worst distance. It is also shown that the result obtained from the formula has a good agreement with the simulation in PSCAD/EMTDC.Keywords
This publication has 10 references indexed in Scilit:
- Lightning protection of low-voltage networks2010
- Effective Protection Distances of Low-Voltage SPD With Different Voltage Protection LevelsIEEE Transactions on Power Delivery, 2009
- Lightning-Induced Overvoltages Transferred Through Distribution Power TransformersIEEE Transactions on Power Delivery, 2008
- Simplified model for estimation of lightning induced transient transfer through distribution transformerInternational Journal of Electrical Power & Energy Systems, 2005
- Evaluation of the Effective Protection Distance of Low-Voltage SPD to EquipmentIEEE Transactions on Power Delivery, 2005
- Simplified three-phase transformer model for electromagnetic transient studiesIEEE Transactions on Power Delivery, 1995
- A high frequency transformer model for the EMTPIEEE Transactions on Power Delivery, 1993
- Transient overvoltage study and model for shell-type power transformersIEEE Transactions on Power Delivery, 1993
- A simplified lumped parameter model for finding distribution transformer and secondary system responses to lightningIEEE Transactions on Power Delivery, 1989
- Transformer model for high frequenciesIEEE Transactions on Power Delivery, 1988