Fault induced conductor motion
Authors:
- D. J. WardDWD. J. Ward
- J. D. BruceJBJ. D. Bruce
- 1 January 2007
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 488-492
Abstract
In utility protective relaying, faults or short-circuits on overhead distribution lines frequently cause conductor movement, which results in a subsequent fault closer to the source. Very often a backup protective device operates for these conditions leading to the suspicion that the coordination of the protective devices is improper. Under phase-to-phase faults, the more frequent situation involving this phenomenon, the conductors are forced apart by the short-circuit forces. Even though the closest protective device (recloser) operates, the conductor motion often bring the conductors together. Thus, one would get a recloser operation as well as a circuit breaker operation. In some cases, the circuit breaker locks out for this situation. As a result, a much larger area is interrupted. This paper builds upon a modeling effort to match what happens in the field and to determine what remedies have the best chance of success in dealing with fault-induced conductor motion (FICM). The authors investigated some real-world examples that occurred on the distribution system and evaluated alternatives to deal with them.Keywords
This publication has 2 references indexed in Scilit:
- Overhead distribution conductor motion due to short-circuit forcesIEEE Transactions on Power Delivery, 2003
- An Analysis of VEPCO'S 34.5 KV Distribution Feeder Faults as Related to Through Fault Failures of Substation TransformersIEEE Transactions on Power Apparatus and Systems, 1978