A Model for Uprating Transmission Lines by Using HTLS Conductors
Authors:
- 16 June 2011
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 26 (4) , 2180-2188
Abstract
This paper presents a new method for calculating tensions and sags on a tension section with different conductors on level and nonlevel spans of equal or unequal lengths and at any temperature, including the situation where the conductor temperature varies on the entire tension section. The model involves the application of high-temperature low-sag conductors on specific spans. As the conductor temperature and electrical current are intrinsically associated with ground clearances, a comparative study of steady-state ampacity models and a sensibility analysis with meteorological parameters were performed. This method results in a gain of ground clearance as well as horizontal tensions less than those calculated for the original line, depending on the type of floating dead end used. The results of a cost-benefit analysis prove very attractive, since the original conductors would not be discarded. Added to which, the large-scale installation of new towers is not necessary. The developed model represents, therefore, a significant contribution to low-cost uprating of transmission lines while, at the same time, avoiding the need to expand the transmission system.Keywords
This publication has 10 references indexed in Scilit:
- Methods for increasing the rating of overhead lines2005
- Increasing power transfer capability of existing transmission lines2004
- Overhead Power Lines2003
- High-temperature conductors: a solution in the uprating of overhead transmission lines2002
- A new generation of high performance conductors2001
- Sag and tension calculations for overhead transmission lines at high temperatures-modified ruling span methodIEEE Transactions on Power Delivery, 2000
- Limitations of the ruling span method for overhead line conductors at high operating temperaturesIEEE Transactions on Power Delivery, 1999
- A proposed design for the new Furnas 500 kV transmission lines-the High Surge Impedance Loading LineIEEE Transactions on Power Delivery, 1999
- Development of Extremely-Low-Sag Invar Reinforced ACSR (XTACIR)IEEE Transactions on Power Apparatus and Systems, 1981
- Sag Calculations for Transmission LinesTransactions of the American Institute of Electrical Engineers, 1926