A Hybrid Islanding Detection Technique Using Average Rate of Voltage Change and Real Power Shift
Authors:
- 4 March 2009
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 24 (2) , 764-771
Abstract
The mainly used islanding detection techniques may be classified as active and passive techniques. Passive techniques don't perturb the system but they have larger non-detection zones, whereas active techniques have smaller non-detection zones but they perturb the system. In this paper, a new hybrid technique is proposed to solve this problem. An average rate of voltage change (passive technique) has been used to initiate a real power shift (active technique), which changes the real power of distributed generation (DG), when the passive technique cannot have a clear discrimination between islanding and other events in the system. Simulation results show that the proposed method is effective in detecting islanding of distribution systems with DGs.Keywords
This publication has 18 references indexed in Scilit:
- Intelligent-Based Approach to Islanding Detection in Distributed GenerationIEEE Transactions on Power Delivery, 2007
- An Islanding Detection Method for Distributed Generations Using Voltage Unbalance and Total Harmonic Distortion of CurrentIEEE Transactions on Power Delivery, 2004
- A new islanding detection algorithm for distributed generations interconnected with utility networks2004
- Development of a logical rule-based islanding detection method for distributed resources2003
- Method for preventing islanding phenomenon on utility grid with a number of small scale PV systems2002
- Using power line carrier communications to prevent islanding [of PV power systems]2002
- Predicting islanding operation of gridconnected PV invertersIEE Proceedings - Electric Power Applications, 2000
- Analysis and performance assessment of the active frequency drift method of islanding preventionIEEE Transactions on Energy Conversion, 1999
- Loss-of-mains detection for small generatorsIEE Proceedings - Electric Power Applications, 1996
- Case study on the integration of a non-utility induction generator to the Hydro-Quebec distribution networkIEEE Transactions on Power Delivery, 1995