Abstract
An active islanding detection technique for an inverter-based distributed generator (DG) is presented. Two control strategies are studied: one in which the DG only supplies active power and one in which the DG supplies both active and reactive power to improve the power factor. The nondetection zone (NDZ) of the over/under voltage and frequency protection (OVP/UVP and OFP/UFP) method for each control strategy is determined. For the presented interface control, it is observed that the NDZ of the OVP/UVP and OFP/UFP is larger when the DG interface is designed to improve the power factor. In order to decrease the NDZ, an islanding detection method is designed that is based on creating a mismatch between the load and DG reactive power, thus forcing the frequency to deviate outside the OFP/UFP limits. It is shown that the proposed islanding detection technique is robust and has a negligible NDZ.Keywords
This publication has 6 references indexed in Scilit:
- Distributed Generation as Voltage Support for Single Wire Earth Return SystemsIEEE Transactions on Power Delivery, 2004
- An Islanding Detection Method for Distributed Generations Using Voltage Unbalance and Total Harmonic Distortion of CurrentIEEE Transactions on Power Delivery, 2004
- Flexible distributed generation: (FDG)2003
- New loss of mains detection algorithm for embedded generation using rate of change of voltage and changes in power factors2001
- Analysis and performance assessment of the active frequency drift method of islanding preventionIEEE Transactions on Energy Conversion, 1999
- Control strategy for grid-connected DC-AC converters with load power factor correctionIEE Proceedings - Generation, Transmission and Distribution, 1998