Abstract
Medium voltage SiC devices facilitate direct (without 50/60 Hz transformer) connection of the power electronics converter to the medium voltage grid using simple topology. Compared to the insulation design of medium voltage inductors that have been widely used in the power system, the insulation design of the medium voltage converter filter inductors has new challenges. Particularly, the grid impact on insulation requirements on converter filter inductors is rarely discussed. This paper introduces the insulation design of a grid-side filter inductor for a 13.8 kV power conditioning system converter. The grid insulation requirements, including the short-duration power frequency overvoltage and the lightning impulse voltage, are considered in the design. To meet the requirements, the layer-to-layer insulation, winding-to-core/ground insulation, the air gap discharge between the winding and the core, the local electric field, as well as the inter-turn transient voltage distribution are considered. The designed inductors are validated by the 46 kV (>1 minute) dc hi-pot test, 12 kV ac partial discharge test, one-hour single-phase converter full rating test, as well as three-phase converter full rating test.
Funding Information
  • Advanced Manufacturing Office
  • United States Department of Energy (DE-EE0008410)
  • Engineering Research Center Program of the National Science Foundation
  • Department of Energy under NSF (EEC-1041877)
  • CURENT Industry Partnership Program

This publication has 14 references indexed in Scilit: