Validity of the voltage-temperature relation for contact elements in high power applications
Authors:
- 1 October 2015
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 29-38
Abstract
With the voltage-temperature (V-T) relation, established by Kohlrausch in 1900, the electric potential distribution in an arbitrarily shaped, thermally insulated, current carrying conductor can be used to calculate the associated temperature distribution. An important application is the determination of the maximum temperature in electric contacts. However, researchers found deviations from the V-T relation for large contact systems when heat dissipation to the environment via radiation and convection becomes significant. The present investigation aims to verify the applicability of the V-T relation to typical spring-loaded contact elements for high power applications as for instance plug-in connections in highvoltage switchgear. A connector with a variable cooling system was continuously loaded with currents up to 6.7 kA to create a multitude of thermally symmetric and asymmetric steady-state operating points. Contact element temperatures were measured and compared to calculations with the V-T relation. When the load current varies over time, the spatially distributed heat capacity of the contact element and the adjacent conductors is charged or discharged to reach the electric-thermal steady-state for which the V-T relation applies. The transient temperature distribution may differ significantly, which is demonstrated by numerical calculations.Keywords
This publication has 12 references indexed in Scilit:
- Electric-thermal performance of contact elements in high power plug-in connections2014
- A Multiphysics Finite Element Model of a 35A Automotive Connector Including Multiscale Rough Surface ContactJournal of Electronic Packaging, 2012
- A Multi-Physics Finite Element Analysis of Round Pin High Power Connectors2010
- Optimal design of generator circuit breakers up to a capacity of 2000 MVA using thermal models2004
- Simulations of transient thermal and electrical behavior of contact spots1999
- Applicability and correction of temperature-voltage relation in the case of point contactIEEE Transactions on Components, Packaging, and Manufacturing Technology: Part A, 1998
- Applicability and correction of temperature-voltage relation in the case of line contactIEEE Transactions on Components, Packaging, and Manufacturing Technology: Part A, 1996
- On the Evalutation of Contact Temperature from Potential-Drop MeasurementsIEEE Transactions on Components, Hybrids, and Manufacturing Technology, 1983
- Electrical conduction in solids II. Theory of temperature-dependent conductorsProceedings of the Royal Society of London. A. Mathematical and Physical Sciences, 1958
- Ueber den stationären Temperaturzustand eines elektrisch geheizten LeitersAnnalen der Physik, 1900