Analysis of the Surface Electric Field Distribution of a 10 kV Faulty Composite Insulator
Open Access
- 15 November 2022
- journal article
- research article
- Published by MDPI AG in Electronics
- Vol. 11 (22) , 3740
Abstract
To obtain a more comprehensive knowledge of the surface electric field distribution of composite insulators, a three-dimensional (3D) simulation model of a 10 kV FXBW4-10/70 composite insulator was established, and the distribution of the axial and radial electric fields on the surface of the insulator under normal, damaged, internal defect, and fouling fault conditions were calculated and analyzed based on the finite element method. The results showed that the axial and radial electric field distributions on the surfaces of the normal composite insulators were “U” shaped, the radial electric field at the damaged location had a greater change than the axial electric field, and both the axial and radial electric fields at the internal defect location increased significantly. For the insulator covered with NaCl conductive fouling, the axial electric fields at the high-voltage (HV) and low-voltage (LV) ends showed a greater change. The results can provide a basis for the fault identification of composite insulators and the optimal design of insulation structures.Keywords
Funding Information
- National Natural Science Foundation of China (62162034)
- National Natural Science Foundation of China (202201AT070189)
- Basic research program key project of Yunnan province (202101AS070016)
This publication has 21 references indexed in Scilit:
- Electric field distribution of optimized composite insulator profiles under different pollution conditionsAin Shams Engineering Journal, 2018
- Numerical investigation of electric field distortion induced by internal defects in composite insulatorsHigh Voltage, 2017
- Study on the flashover performance of various types of insulators polluted by nitratesIEEE Transactions on Dielectrics and Electrical Insulation, 2017
- Heating phenomenon in unclean composite insulatorsEngineering Failure Analysis, 2016
- Effects of pollution materials on the AC flashover performance of suspension insulatorsIEEE Transactions on Dielectrics and Electrical Insulation, 2015
- Failure analysis of decay-like fracture of composite insulatorIEEE Transactions on Dielectrics and Electrical Insulation, 2014
- Influences of Electric-Field Distribution Along the String on the Aging of Composite InsulatorsIEEE Transactions on Power Delivery, 2013
- High-Voltage Insulators Mechanical Load Limits—Part II: Standards and RecommendationsIEEE Transactions on Power Delivery, 2012
- Electric Fields on AC Composite Transmission Line InsulatorsIEEE Transactions on Power Delivery, 2008
- Can water cause brittle fracture failures of composite non-ceramic insulators in the absence of electric fields?IEEE Transactions on Dielectrics and Electrical Insulation, 2004