State space formulation and transient stability of the double output asynchronous generator
- 1 January 1993
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Energy Conversion
- Vol. 8 (4) , 732-738
Abstract
The double output asynchronous generator state space formulation by using the small displacement procedure valid for both grid connected and for autonomous systems is deduced. The study of the dynamics shows that the transient stability is influenced by disturbances of speed of load and of excitation frequency for any rms value and power factor of the excitation voltage. Because of its linearity the small displacement model in state space form can be used for control design purposes. From the matrices in generalized form, the transfer functions needed for the design of frequency and current controllers are easily computedKeywords
This publication has 7 references indexed in Scilit:
- Determination of frequencies in autonomous double output asynchronous generatorIEEE Transactions on Energy Conversion, 1992
- Doubly fed induction machine state variables model and dynamic responseIEEE Transactions on Energy Conversion, 1991
- Reference frame analysis of a slip energy recovery systemIEEE Transactions on Energy Conversion, 1988
- Control of Control of Cascaded Doubly Fed Machines for Generator ApplicationsIEEE Transactions on Power Apparatus and Systems, 1984
- A Simplified Approach to the Determination of Induction Machine Dynamic ResponseIEEE Transactions on Power Apparatus and Systems, 1978
- Induction machine transfer functions and dynamic response by means of complex time variablesIEEE Transactions on Power Apparatus and Systems, 1976
- The General Theory of Alternating Current Machines1975