Condition Monitoring of Distribution Transformers Using Frequency Response Traces and Artificial Neural Network to Detect the Extent of Windings Axial Displacements
Authors:
- 11 May 2022
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 18-23
Abstract
Distribution transformers are of great importance in power systems regarding electrical power supply to the consumers. To have a reliable and continuous service, monitoring of transformers is a crucial issue. Maloperation or improper transportation can result in mechanical tension and stress on transformer windings. Axial displacement (AD) is one of the mechanical defects that can influence transformer operation through windings insulation degradation and short circuit faults. Frequency response analysis (FRA) is an efficient diagnostic technique widely used in transformers monitoring; however, interpretation of FRA results is complicated and is still under investigation. In this paper, AD faults are implemented on the 20 kV winding of a 1600 kV A distribution transformer. FRA traces are practically measured, and then the most sensitive and appropriate statistical indices such as cross-correlation factor (CCF), Lin's concordance coefficient (LCC), sum of errors (SE), and fitting percentage (FP) are employed to extract feature sets. All four components of the frequency responses, i.e., magnitude, phase, real and imaginary parts, are considered. Furthermore, an Artificial Neural Network using the obtained feature vectors is designed to detect the extent of the AD faults. The K-fold cross-validation method is used to evaluate the performance of the intelligent classifier. Both of the most suitable statistical indexes and frequency response components to detect the AD faults are determined.Keywords
This publication has 24 references indexed in Scilit:
- Diagnosis and clustering of power transformer winding fault types by cross‐correlation and clustering analysis of FRA resultsIET Generation, Transmission & Distribution, 2018
- Causes of transformer failures and diagnostic methods – A reviewRenewable and Sustainable Energy Reviews, 2018
- Frequency response analysis (FRA) of transformers as a tool for fault detection and location: A reviewElectric Power Systems Research, 2018
- Detection of Power Transformer Winding Deformation Using Improved FRA Based on Binary Morphology and Extreme Point VariationIEEE Transactions on Industrial Electronics, 2017
- Novel Calculation Method of Indices to Improve Classification of Transformer Winding Fault Type, Location, and ExtentIEEE Transactions on Industrial Informatics, 2017
- Transformer winding fault detection by vibration analysis methodsApplied Acoustics, 2016
- A survey on statistical indexes applied on frequency response analysis of electric machinery and a trend based approach for more reliable resultsElectric Power Systems Research, 2016
- Sensitivity Analysis of k-Fold Cross Validation in Prediction Error EstimationIEEE Transactions on Pattern Analysis and Machine Intelligence, 2009
- A practical example of power transformer unit winding condition assessment by means of short-circuit impedance measurement2009
- Transfer function method to diagnose axial displacement and radial deformation of transformer windingsIEEE Transactions on Power Delivery, 2003