Management of Microbiological Contamination of the Water Network of a Newly Built Hospital Pavilion
Authors:
- Osvalda De GiglioOsvalda De Giglio
- Giusy DiellaGiusy Diella
- Marco LopuzzoMLMarco Lopuzzo
- Francesco TriggianoFrancesco Triggiano
- Carla CaliaCarla Calia
- Chrysovalentinos PousisCPChrysovalentinos Pousis
- Fabrizio FasanoFabrizio Fasano
- Giuseppe CalabreseGCGiuseppe Calabrese
- Vincenza RafaschieriVRVincenza Rafaschieri
- Lucia Federica CarpagnanoLCLucia Federica Carpagnano
- Matilde CarlucciMCMatilde Carlucci
- Loreto GesualdoLGLoreto Gesualdo
Open Access
Abstract
The good installation, as well as commissioning plan, of a water network is a crucial step in reducing the risk of waterborne diseases. The aim of this study was to monitor the microbiological quality of water from a newly built pavilion before it commenced operation. Overall, 91 water samples were tested for coliforms, Escherichia coli, enterococci, Pseudomonas aeruginosa and Legionella at three different times: T0 (without any water treatment), T1 (after treatment with hydrogen peroxide and silver ions at initial concentration of 20 mg/L and after flushing of water for 20 min/day for seven successive days) and T2 (15 days later). Coliforms were detected in 47.3% of samples at T0, 36.3% at T1 and 4.4% at T2. E. coli was isolated in 4.4% of the samples only at T1, while enterococci appeared in 12.1% of the samples at T1 and in 2.2% at T2. P. aeruginosa was isolated in 50.5% of the samples at T0, 29.7% at T1 and 1.1% at T2. Legionella pneumophila serogroup 8 was isolated in 80.2% of the samples at T0, 36.3% at T1 and 2.2% at T2. Our results confirmed the need for a water safety plan in new hospital pavilions to prevent the risk of waterborne diseases.Keywords
Funding Information
- Regional Epidemiological Observatory, Apulia, Italy (D.G.R. 137/2017-21,2019)
This publication has 33 references indexed in Scilit:
- Epidemiology of invasive fungal infections in the intensive care unit: results of a multicenter Italian survey (AURORA Project)Infection, 2013
- Invasive Fungal Infections in Patients with Hematologic Malignancies (Aurora Project): Lights and Shadows During 18-Months SurveillanceInternational Journal of Molecular Sciences, 2012
- Asset deterioration and discolouration in water distribution systemsWater Research, 2011
- Legionella spp. and legionellosis in southeastern Italy: disease epidemiology and environmental surveillance in community and health care facilitiesBMC Public Health, 2010
- Microbial diversity in biofilms on water distribution pipes of different materialsWater Science & Technology, 2010
- Variable bacterial load of Legionella spp. in a hospital water systemScience of The Total Environment, 2009
- Outbreak of Multidrug-ResistantPseudomonas aeruginosaColonization and Infection Secondary to Imperfect Intensive Care Unit Room DesignInfection Control & Hospital Epidemiology, 2009
- Disinfection of Burkholderia cepacia complex from non-touch taps in a neonatal nurseryJournal of Perinatal Medicine, 2008
- Prevention and control of health care–associated waterborne infections in health care facilitiesAmerican Journal of Infection Control, 2005
- LEGIONNAIRES' DISEASE IN A TRANSPLANT UNIT: ISOLATION OF THE CAUSATIVE AGENT FROM SHOWER BATHSThe Lancet, 1980