In accordance with South Korea’s recent 2030 Carbon Neutral Plan, an 8GW offshore wind farm is planned for construction in the South-west Sea. Therefore, it is expected that large-scale wind turbines will be installed, and these turbines must operate stably, even when there are instantaneous voltage fluctuations in the power system. The grid code is described for the low-voltage-ride-through (LVRT) and high-voltage-ride-through (HVRT) functions, and a test facility that can perform both LVRT and HVRT tests is essential. In the case of LVRT/HVRT test facilities developed by the existing RLC (impedance component) method, it may be difficult to test large-scale wind turbines due to problems such as power quality, frequent failures and narrow short-circuit capacity ranges. Therefore, to solve such problems, this paper proposes an LVRT/HVRT test facility of the autotransformer type, which is capable of outputting the desired voltage range by changing the wiring method and tap position. Specifically, in order to implement the test facility of the autotransformer type, which is able to output the desired voltage range by changing the wiring method and tap according to the LVRT/HVRT test status, this paper presents an impedance determination algorithm (two-step layer impedance determination algorithm) of auto-transformer based on the fault-current analysis and operation strategy at a real LVRT/HVRT testing evaluation facility.Keywords
Funding Information
- Ministry of Trade, Industry, and Energy and supported by the Korea Institute of Energy Technology Evaluation and Planning (KETEP) (20223030020110, C3-2416-01)
- Research and Development Program of the Korea Institute of Energy Research (KIER) (20223030020110, C3-2416-01)
This publication has 11 references indexed in Scilit:
- Improved Control of Grid-connected DFIG-based Wind Turbine using Proportional-Resonant Regulators during Unbalanced GridEnergies, 2019
- Synchronization and Reactive Current Support of PMSG-Based Wind Farm During Severe Grid FaultIEEE Transactions on Sustainable Energy, 2018
- Low Voltage Ride-through Scheme of the PMSG Wind Power System Based on Coordinated Instantaneous Active Power ControlEnergies, 2017
- Assessment and Enhancement of a Full-Scale PMSG-Based Wind Power Generator Performance Under FaultsIEEE Transactions on Energy Conversion, 2016
- Benchmarking of Voltage Sag Generators2012
- Inverter based voltage sag generator with PR-controller2012
- LVRT Scheme of PMSG Wind Power Systems Based on Feedback LinearizationIEEE Transactions on Power Electronics, 2012
- Transformer based voltage sag generator to perform LVRT and HVRT tests in the laboratory2010
- A three-phase programmable voltage sag generator for low voltage ride-through capability test of wind turbines2010
- Test Bench for Grid Code Simulations for Multi-MW Wind Turbines, Design and ControlIEEE Transactions on Power Electronics, 2008