Improving Differential Relay Performance during Cross-Country Fault Using a Fuzzy Logic-based Control Algorithm
Authors:
- 1 February 2019
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 193-199
Abstract
This paper presents a fuzzy logic-based algorithm to improve the performance of the differential relay in short transmission line protection for Cross-Country faults. This type of faults leads to the malfunction of current differential relays, while the probability of the relay performance error becomes negligible by using a fuzzy logic system along with the changes in per-unit values and the slope of the differential relay, and consequently choosing the best stability characteristics. In the proposed algorithm, the sensitivity, operation reliability, and performance speed for several types of faults including internal faults and even the high-resistive faults are maintained in the satisfactory levels. The algorithm is also suitable for external faults with the saturation of current transformers (CTs), and it improves the relay performance. The effectiveness of the algorithm is verified in EMTDC/PSCAD software program, and the obtained results are compared with those of conventional methods.Keywords
This publication has 11 references indexed in Scilit:
- Determining the contribution of different effective factors to individual voltage unbalance emission in n-bus radial power systemsInternational Journal of Electrical Power & Energy Systems, 2018
- Modeling and numerical simulations of the influenced Sznajd modelPhysical Review E, 2017
- Fuzzy-GA based algorithm for optimal placement and sizing of distribution static compensator (DSTATCOM) for loss reduction of distribution network considering reconfigurationJournal of Central South University, 2017
- Dynamics of a Repulsive Voter ModelIEEE Transactions on Computational Social Systems, 2016
- Fuzzy Adaptive Transmission-Line Differential Relay Immune to CT SaturationIEEE Transactions on Power Delivery, 2012
- A Current Differential Relay for a 1000-kV UHV Transmission LineIEEE Transactions on Power Delivery, 2007
- Fuzzy-Logic-Based Fault Classification Scheme for Digital Distance ProtectionIEEE Transactions on Power Delivery, 2005
- Fuzzy logic systems for engineering: a tutorialProceedings of the IEEE, 1995
- Charge comparison protection of transmission lines-communications conceptsIEEE Transactions on Power Delivery, 1992
- Development of a PCM Current Differential Relaying System Using Fiber-Optic Data TransmissionIEEE Transactions on Power Apparatus and Systems, 1984