Study of phase reactances of special-purpose transformers during diagnostics of the excitation system of the electromagnetic scattering field
Authors:
- Volodymyr ZinovkinVZVolodymyr Zinovkin
- Andrii TretiakovATAndrii Tretiakov
Open Access
- 9 July 2025
- journal article
- Published by National Technical University Kharkiv Polytechnic Institute in Bulletin of the National Technical University "KhPI". Series: Energy: Reliability and Energy Efficiency
- No. 1(10),p. 23-30
Abstract
The study of phase reactances of special-purpose transformers was conducted for the diagnostics of electromagnetic scattering excitation systems. Special attention is paid to assessing the technical condition of power transformers that supply energy-intensive technological complexes, as the current and voltage in them change according to complex periodic laws, leading to asymmetrical modes and accidents. To improve the reliability of transformer equipment, there is a need to develop specialized microprocessor and software tools for automated analysis and prevention of failures. Accident analysis has shown that electromagnetic scattering excitation systems are the most frequently damaged elements. A methodology for investigating the phase short-circuit resistances of power transformers with complex galvanic winding connections without disassembling the tank is proposed. The research aims to obtain reliable information about the current technical condition of transformer windings based on measured external parameters. The scientific novelty lies in establishing analytical dependencies between interphase short-circuit resistances and phase resistances. The developed program algorithm for automated analysis of winding conditions was implemented in “Turbo Pascal”. Experimental studies on a TRDN-63000/150/35 transformer confirmed the accuracy of the methodology and revealed deformation of the low voltage winding. The predominant causes of winding damage include charring and polymerization of inter-turn insulation due to excessive electrical load. The proposed method allows for the detection of deformations without disassembling transformers, which is useful in multi-parameter diagnostic systems to prevent emergencies. Further research is needed to integrate this approach with other diagnostic and automation methods. The methodology can be applied to multi-winding transformers with a “star-delta-delta” winding connection scheme.Keywords
This publication has 18 references indexed in Scilit:
- Transformer Diagnostics and Maintenance: Practical Indications Derived from a Large Transmission SystemIEEE Electrical Insulation Magazine, 2024
- Advances in DGA based condition monitoring of transformers: A reviewRenewable and Sustainable Energy Reviews, 2021
- Intelligent Machine Learning Techniques for Condition Assessment of Power Transformers2020
- Physical simulation of electromagnetic phenomena in transformer equipment under strongly varying loads2017
- Research of non-stationary electromagnetic processes in synchronous electric drive2017
- PDTools: A toolbox of partial discharge (PD) signal analysis for transformer condition assessment2017
- Review of torque ripple minimization in PM synchronous motor drives2008
- Dielectric response methods for diagnostics of power transformersIEEE Electrical Insulation Magazine, 2003
- Controller-induced parasitic torque ripples in a PM synchronous motorIEEE Transactions on Industry Applications, 2002
- Direct estimation of the generalised equivalent circuits of synchronous machines from short-circuit oscillographsIEE Proceedings C Generation, Transmission and Distribution, 1990