Optimization of Ampacities for Unequally Loaded Underground Power Cables
Authors:
- 1 July 1982
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Apparatus and Systems
- Vol. PAS-101 (7) , 2348-2354
Abstract
Underground power cable systems often contain different types of cables with unequal currents. Programs which calculate cable ampacities and temperatures need to be able to maximize these unequal currents subject to the temperature restrictions on each cable's insulation. This paper presents an optimization routine to maximize the currents for unequally loaded cable systems using the reduced gradient method. The computational algorithm also considers the temperature dependence of the conductor electrical resistances in determining cable ampacities and temperatures.Keywords
This publication has 1 reference indexed in Scilit:
- The calculation of the temperature rise and load capability of cable systemsTransactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems, 1957