Fault Location for Single-Circuit Line Based on Bus-Impedance Matrix Utilizing Voltage Measurements
Author:
- 31 March 2008
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 23 (2) , 609-617
Abstract
Diverse transmission line fault location algorithms have been proposed in the past depending on measurements available. Existing algorithms usually require measurements captured from buses of a faulted line. By taking advantage of the bus-impedance matrix technique, this paper presents a possible fault location approach for single-circuit lines utilizing only voltage measurements from one or two buses, which may be distant from the faulted line. With the addition of a fictitious bus where the fault occurs, the transfer impedances of this bus and other buses are revealed as a function of the fault location. Based on the relationship between the bus voltage change due to fault and the transfer impedance, the fault location can be derived. Shunt capacitance of the line is ignored first and then fully considered based on distributed parameter line model. Electromagnetic transients program simulation studies have shown quite encouraging results.Keywords
This publication has 21 references indexed in Scilit:
- Fault Location Utilizing Unsynchronized Voltage Measurements During FaultElectric Power Components and Systems, 2006
- Best ANN Structures for Fault Location in Single- and Double-Circuit Transmission LinesIEEE Transactions on Power Delivery, 2005
- Fault Location Scheme for a Multi-Terminal Transmission Line Using Synchronized Voltage MeasurementsIEEE Transactions on Power Delivery, 2005
- A New PMU-Based Fault Detection/Location Technique for Transmission Lines With Consideration of Arcing Fault Discrimination—Part I: Theory and AlgorithmsIEEE Transactions on Power Delivery, 2004
- Fault location using voltage measurementsIEEE Transactions on Power Delivery, 2002
- Fault location using the distributed parameter transmission line modelIEEE Transactions on Power Delivery, 2000
- Distance protection and fault location utilizing only phase current phasorsIEEE Transactions on Power Delivery, 1998
- Development of an advanced transmission line fault location system. II. Algorithm development and simulationIEEE Transactions on Power Delivery, 1992
- Development of an advanced transmission line fault location systems. I. Input transducer analysis and requirementsIEEE Transactions on Power Delivery, 1992
- Accurate fault location technique for power transmission linesIEE Proceedings C Generation, Transmission and Distribution, 1990