Abstract
Distributed energy resources (DER) such as solar photovoltaics (PV) are required to achieve a high performance and an efficient use of generated renewable power in grid-integrated applications, both in normal and fault operating conditions. In this paper, a grid-following multi-functional control strategy for a three-phase three-level T-type quasi-impedance source inverter (3L-T-type qZSI) is studied through simulation and experimental tests. The grid-following functionality is achieved by a PI-based dq current controller for the active and the reactive power tracking. A PI-based dc controller is used for the dc-link voltage control by taking advantage of the quasi-impedance source network ability for input voltage boosting. The dc-ac power conversion is accomplished through a space vector pulse-width modulation (SVPWM) with inner capacitors voltages balancing capability and minimum common-mode voltage generation. Besides, a low voltage ride-through strategy was implemented to fulfill the fault requirements imposed by the Spanish standard. The simulation and experimental results demonstrate the above-mentioned functionalities and validate the stability and good dynamic response of the grid-connected 3L-T-type qZSI. Thus, this work supposes a novel contribution due to the few works previously reported in the literature concerning the performance of this relatively recent inverter topology in grid-tied applications.
Funding Information
  • Junta de Extremadura (IB20165)
  • Program Ayudas Talento (TA18003)
  • Funding for Research Groups (GR21162)
  • National (Portugal) Funds Through Fundação para a Ciência e a Tecnologia (UIDB/50021/2020)

This publication has 38 references indexed in Scilit: