The UHF technique of ,detecting ,partial discharges in gas insulated substations (GIS), has,over ,the past 10 years ,or so ,been developed,from ,a laboratory ,curiosity into a sensitive means ,of giving ,an early ,warning ,of most impending,failures in the substation. Its rapid,acceptance ,by both ,utilities and switchgear,manufacturers ,worldwide ,has resulted from it being a simple, sensitive and practical technique. In addition, utilities are finding it necessary ,to drive their plant harder and need to be,assured of its reliability – even though they may,have fewer staff to carry out maintenance,work. The UHF technique is now seen by them ,as a ,cost effective means ,of avoiding failures, and providing the high quality,of supply ,demanded ,by today's customers. The principle of the UHF technique is that the current pulse which forms the partial discharge has a very short risetime, and this excites the GIS chambers ,into multiple ,resonances ,at frequencies of up,to 1.5 GHz or so. Although the duration of the current pulse is only,a few