Protection of Line Faults in HVDC Grids Through Convexity Detection in Backward Traveling Wave Voltages
- 16 June 2023
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 38 (5) , 3660-3676
Abstract
Short-circuit faults in high-voltage DC (HVDC) grids must be timely isolated. Conventional fault isolation schemes for HVDC grids typically rely on numerical simulations or analytical calculations for threshold setting, which complicate engineering implementation. To solve this issue, this paper first introduces the convex point of backward traveling wave (BTW) voltage as the reference for the faulty line isolation in HVDC grids, which is interpreted as the singular feature in the second derivative (SD) of BTW voltage. The singularity in the SD of BTW voltage is independent of system or fault parameters, having good generality in HVDC grids. Through recognizing the unique pattern in the wavelet transform modulus maxima of the singular feature, the proposed protection method can identify faulty lines in HVDC grids in the initial phase of faults. Numerical studies carried out with PSCAD/EMTDC and MATLAB/Simulink demonstrate the effectiveness, robustness and applicability of the proposed method in detecting and isolating various single- and double-pole faults in HVDC grids.Keywords
Funding Information
- National Natural Science Foundation of China (52107124)
This publication has 46 references indexed in Scilit:
- Selective Nonunit Protection Technique for Multiterminal VSC-HVDC GridsIEEE Transactions on Power Delivery, 2017
- A non-communication based protection algorithm for multi-terminal HVDC gridsElectric Power Systems Research, 2017
- Current differential protection principle of HVDC transmission systemIET Generation, Transmission & Distribution, 2017
- Transient-Voltage-Based Protection Scheme for DC Line Faults in the Multiterminal VSC-HVDC SystemIEEE Transactions on Power Delivery, 2016
- DC Fault Detection and Location in Meshed Multiterminal HVDC Systems Based on DC Reactor Voltage Change RateIEEE Transactions on Power Delivery, 2016
- A New Differential Protection of Transmission Line Based on Equivalent Travelling WaveIEEE Transactions on Power Delivery, 2016
- An Improved Traveling-Wave Protection Scheme for LCC-HVDC Transmission LinesIEEE Transactions on Power Delivery, 2016
- Nonunit Protection of HVDC Grids With Inductive DC Cable TerminationIEEE Transactions on Power Delivery, 2015
- Fault Detection and Interruption in an Earthed HVDC Grid Using ROCOV and Hybrid DC BreakersIEEE Transactions on Power Delivery, 2014
- Development of a Novel Protection Device for Bipolar HVDC Transmission LinesIEEE Transactions on Power Delivery, 2014