ESTIMATION OF THE RATIO OF THE REQUIRED MINIMUM FIRE PROTECTION THICKNESS OF STEEL STRUCTURES UNDER DIFFERENT NOMINAL FIRE TEMPERATURE-TIME CURVE

Authors:
  • CUCherkasy Institute of Fire Safety named after Chornobyl Heroesof National University of Civil Protection of Ukraine
    Cherkasy Institute of Fire Safety named after Chornobyl Heroesof National University of Civil Protection of Ukraine
  • MPMaksym Pustovyi
    Maksym Pustovyi
  • IPInstitute of Public Administration and Research in Civil Protection
    Institute of Public Administration and Research in Civil Protection

Abstract
Given the lack of certainty and practical significance of the data on the relationship between the required minimum thickness of fire protection systems for steel structures under different nominal fire temperature-time curve, research aimed at further improving and developing methods for assessing this thickness at different levels of thermal exposure, reflecting different fire scenarios, as well as methods for determining this relationship, is currently relevant. The purpose of the study was to substantiate a method for determining this ratio, suitable for obtaining reliable results for the evaluation of passive and reactive fire protection systems for steel structures. To achieve this goal, the task was set to substantiate the components of this method and its procedures.The essence of the method proposed in this paper is to test a set of loaded and unloaded structures at a standard temperature-time curve, determine the thermal properties of the fire protection material used, calculate the required minimum fire protection thickness for different nominal temperature-time curveand the ratio between these thicknesses based on the data obtained on these properties.This method employs a number of procedures, some of which are standardized and some of which are not. The standardized procedures include procedures for selecting and testing structural specimens, adjusting the time intervals until design temperatures are reached due to differences in test specimen parameters and "adhesion" values, and selecting the range and parameters of steel structures to determine the required minimum fire protection thickness.Non-standardized procedures are used to adjust the time intervals for loaded structures and short structures for comparison, which were heated during different tests, as well as procedures for determining the thermal properties of the fire protection material and calculating the required minimum thickness of fire protection. The rationale for using these procedures in the proposed method is given.Keywords: fire protection material, fire protection thickness, fire protection system, steel structure, temperature-time curve, thermal properties